CCR-23 Rectifier Controller Communication Driver is the driver to communicate with rectifier controller of WonBang C & C in Korea.
<Figure 1> is read setting example of CCR-23 Rectifier Controller communication driver.
		![]()  | 
	
| <Figure 1> Read setting example of CCR-23 Rectifier Controller communication driver | 
Device part of <Figure 1> input Com Port(COM1), Baud Rate(57600), Parity Bit(0), Data Bit(8), Stop Bit(1) respectively.
CCR-23 Rectifier Controller Indicator communication driver¡¯s read schedule
Read schedule setting parameters are as follows:
1) STATION – Controller ID = 0 ~ 255.
2) Read command – Don't care(input blank).
3) Read start address – Don't care.
4) Save start address for Communication Server – Saving start address of Communication Server.
Start Addr + 0 : Version(Fixed to 2),
Start Addr + 1 : Flag( Refer to <Table 1> ),
Start Addr + 2 : Error(( Refer to <Table 2> ),
Start Addr + 3 : Voltage(real value = read value / 10),
Start Addr + 4 : Current(real value = read value / 10),
Start Addr + 5 : Voltage(set, real value = read value / 10),
Start Addr + 6 : Current(set, real value = read value / 10),
Start Addr + 7 ~ 12 : Setup 1 ~ 6.
5) Read Size – Size = Fix to 1. ( Refer to <Table 1> )
Read schedule example)
READ, 3 , , 0, 0, 1,
<Table 1> is a description of Meaning for each bit of 'Flag' value. <Table 2> is a description of Meaning for each bit of 'Error' value.
| bit position | Meaning | 
| 15 (8000h) | ON = Communication error or controller turn off OFF = Normal  | 
  
| 14~8 | -  | 
  
| 7 (80h) | ON = RUN, OFF = STOP  | 
  
| 6 (40h) | ON = SETUP, OFF = RUN/STOP  | 
  
| 5 (20h) | |
| 4 (10h) | ON = Error, OFF = None ERROR  | 
  
| 3 ~ 1 | -  | 
  
| 0 (01h) | ON = time set OK, OFF = don't time set  | 
  
| <Table 1> Meaning for each bit of 'Flag' value | |
bit position  | 
    Meaning  | 
  
15 ~ 13  | 
    -  | 
  
12 (1000h)  | 
    Over Voltage  | 
  
11 (0800h)  | 
    Over Current2  | 
  
10 (0400h)  | 
    Over Current1  | 
  
9 ~ 7  | 
    -  | 
  
6 (40h)  | 
    Controller Error  | 
  
5 (20h)  | 
    Over Temperature  | 
  
4 (10h)  | 
    Fuse Open  | 
  
3 (08h)  | 
    Wire Fault  | 
  
2 ~ 1  | 
    -  | 
  
0 (01h)  | 
    Offset Fail  | 
  
| <Table 2> Meaning for each bit of 'Error' value | |
  If you click the icon 
 in 
protocol option part, you can see the dialogue box such as <Figure 2>. you can 
also set read schedule by using this part.  
		![]()  | 
	
| <Figure 2> Example of CCR-23 Rectifier Controller communication driver¡¯s Option dialogue box | 
You can set read schedule by using 
,
, 
 button and listbox 
of <Figure 2>. 
		![]()  | 
	
| <Figure 3> Example of CCR-23 Rectifier Controller communication driver¡¯s read schedule Add/Edit dialogue box | 
When you click Add button or Edit button in dialogue box of <Figure 2>, dialogue box of <Figure 3> is shown.
CCR-23 Rectifier Controller communication driver don't support writing settings because of read only controller.
Please connect 2, 3, 4, 5( from left 1, 2, .... ) connector of RJ11 RS-485 and Rx-, Rx+, Tx-, Tx+ connector of computer's RS-485.
CCR-23 side computer side
2 ----------------------------- Rx-
3 ----------------------------- Rx+
             
     4
  -----------------------------
  
             
     5
  -----------------------------
  
<Figure 4> is appearance of CCR-23 Rectifier Controller.
		![]()  | 
	
| <Figure 4> Appearance of CCR-23 Rectifier Controller |